Solid Core Station Post Insulator TR-210

Solid Core Station Post Insulator TR-210

Solid Core Station Post Porcelain Insulator TR-210

 

Dimensions
Height (H): 18Inches (457mm)
Diameter(D): 7 1/2Inches (191mm)
Leakage Distance: 37Inches (940mm)

Mechanical Values
Cantilever Strength: 2,000Pounds (8.9kN)
Tensile Strength: 12,000Pounds (53.4kN)
Torsion Strength: 10,000Inch-Pound
Compression Strength: 15,000Pounds (66.8kN)

Electrical Values
Voltage Class:  34.5kV
Impulse Flashover Voltage, Positive: 225kV
Low Frequency Wet Withstand Voltage: 80kV
Impulse Withstand Voltage:  200kV

Radio Influence Voltage Data
Test Voltage RMS to Ground: 22kV
Maximum RIV at 1000 kHz: 100μV

Packing and Shipping Data
Net Weight, Approximate: 15.4kg