Definition of Pin type insulator ANSI 55-4:
Pin type insulator is generally consist of insulation parts,if two parts, which need assembled together with cement. ANSI 55-4 pin type insulator is one of the most commonly used pin type insulator, and ANSI 55-4 pin type insulator belongs to the ceramic insulator.
Technical data:
Type | ANSI 55-4 | ||
Creepage distance-mm | 229 | ||
Flashover voltage-kV | Power frequency | Dry | 65 |
Wet | 35 | ||
50% impulse | Pos. | 105 | |
Neg. | 130 | ||
Radio influence voltage | Test voltage to ground-KV | 10 | |
Max. RIV at 1000kHz-μv | 50 | ||
Low frequency Puncture voltage-kV | 95 | ||
Dry arcing distance-mm | 127 | ||
Cantilever failing load-lb/KN | 3000/13 |
ANSI 55-4 pin type insulator thread type:
1”(25.4mm) porcelain thread type
Assembled spindle or pin for ANSI 55-4 pin type insulator: should fit with 1”(25.4mm) lead head spindle
Neck and groove information:
ANSI 55-4 is “F” neck.
The side-wire groove shall seat a mandrel with a diameter of 1-1/16 inches, but shall not seat a mandrel with a diameter of 1-3/8 inches.
The top-wire groove shall seat a mandrel with a diameter of 1-3/4 inches.
Radio freed ANSI 55-4 high voltage insulator with semi-conductor glaze on the top.
Specifications of ANSI 55-4 pin type insulator:
Model Number: 55-4
Material: Porcelain
Application: High Voltage
color: brown or grey
Brand Name: SENDUO
Standard: Manufactured and Tested to ANSI Standard C29.5
Senduo insulator is a famous insulator trading enterprise, and we supply many types ceramic insulators, composite insulator, HDPE insulators and electric power fittings for transimission line. To satisfy our customers' requirement is our company object. We believe that ANSI 55-4 pin type insulator and other types insulators or fittings you want will not let you down but be a surprise.